Sewer Air Test & Manhole Vacuum Test Timer

Required hold times for low-pressure air testing of gravity sewer and vacuum testing of manholes, with a countdown timer. Runs entirely offline; inputs persist in this browser via localStorage.

Safety — read before pressurizing anything: Compressed air in a plugged pipe stores real energy; plug blowouts have killed people. Brace or restrain all plugs against the thrust, never position anyone in a manhole or in line with a plug while the line is pressurized, relieve pressure before touching plugs, and read the gauge from grade. Air testing is a no-entry operation, full stop.
Which table governs: The times below are computed from the widely used UNI-B-6 / ASTM F1417 time formula (pipe) and the commonly published ASTM C1244 table (manholes). Standards get revised and specs sometimes adopt modified tables — where your contract documents include a test table, that table governs over this tool.
Low-Pressure Air Test — UNI-B-6 / ASTM F1417 Method

Use whichever the spec calls out. Times for the 0.5 psig method are half the 1.0 psig times.

Gauge pressures must be raised 0.433 psi per foot of groundwater above the crown.

Manhole Vacuum Test — ASTM C1244 Method

Depths between table rows are rounded up to the next 2-ft increment (conservative). Depths over 30 ft are extrapolated — verify against the standard.

--:--
Set the timer from a calculated hold time above.

How the Numbers Are Derived

Air test hold time formula

The UNI-B-6 / ASTM F1417 time for a 1.0 psig drop, based on an allowable air loss of 0.0015 cfm per square foot of internal pipe surface:

T = 0.085 · D · K / Q seconds, where K = 0.000419 · D · L (but not less than 1.0) and Q = 0.0015

with D in inches and L in feet. For K = 1 (short/small sections) this reduces to T = 56.7 · D seconds — the familiar "minimum time" column (e.g. 7 min 34 s for 8-in. pipe at 1.0 psig). Beyond the threshold length L = 2387/D ft, time grows with D²·L. Times for the 0.5 psig drop method are exactly half.

Groundwater adjustment

Groundwater above the pipe pushes back against the escaping air, so all gauge pressures are raised by the equivalent head: 0.433 psi per foot of average groundwater height above the pipe crown. The tool adjusts the pressurization, start, and fail pressures accordingly. When the required adjusted test pressure approaches 9 psig, air testing is generally not advised (plug thrust and safety) — dewater, or test by another method (low-pressure exfiltration, CCTV plus joint testing per the spec).

Vacuum test table

ASTM C1244 tests the assembled manhole (including joints and boots, lift holes plugged) at 10 in. Hg of vacuum; the manhole passes if the vacuum takes at least the tabulated time to drop to 9 in. Hg. Times scale with manhole volume — larger diameter and deeper barrels get longer times. The tool reproduces the commonly published table (8–30 ft depth, 30–72 in. diameter), rounds intermediate depths up to the next row, and linearly extrapolates beyond 30 ft with a warning.

Field notes

References

  1. ASTM F1417 — Standard Practice for Installation Acceptance of Plastic Non-pressure Sewer Lines Using Low-Pressure Air. https://www.astm.org/
  2. Uni-Bell UNI-B-6 — Recommended Practice for Low-Pressure Air Testing of Installed Sewer Pipe. https://www.uni-bell.org/
  3. ASTM C828 (clay) and C924 (concrete) — companion low-pressure air test methods.
  4. ASTM C1244 — Standard Test Method for Concrete Sewer Manholes by the Negative Air Pressure (Vacuum) Test.